FG16OR16 – 0,6/1 kV Signalling and control
DESCRIPTION
SIGNALLING AND CONTROL CABLE, HEPR INSULATED (G16), PVC SHEATHED (R16) , WITH SPECIAL REQUIREMENTS OF REACTION TO FIRE PERFORMANCE ACCORDING TO CONSTRUCTION PRODUCTS REGULATION(CPR)
SHAPE
Round
CONDUCTOR
Flexible annealed bare copper, class 5 according to CEI EN 60228
INSULATION
High modulus ethylene propylene rubber-based HEPR insulation compound with low smoke and acidity according to CEI 20-11/0/1;V1 (G16 quality)
SHEAT
PVC based sheathing compound according to CEI 20-11/0/1;V1 (R16 quality)
MAX MECHANICAL STRESS
5 kg/mm²
MARKING
Ink Jet: PECSO MN FG16OR16 0,6/1 KV (SECTION) CEI-UNEL 35322 – Cca-s3,d1,a3 CE WW/YY (METER MARKING)
COLOR
Core identification according to CEI-UNEL 00722.
VOLTAGE
600/1000 V
MAXIMUM TEMPERATURE ON USE
90° C
MINIMUM TEMPERATURE OF INSTALLATION
0º C
MAXIMUM SHORT CIRCUIT TEMPERATURE
250° C
STANDARDS
CEI EN 60228; CEI 20-11/0-1;V1; CEI 20-13; CEI UNEL 35322; CEI 20-67;
MINIMUM INTERNAL BENDING RADIUS
4xD
CERTIFICATIONS
click on the logos to download the certification
Guide to use
Power supply energy cables suitable for limiting the spread of fire. Suitable for bundled installations in environments such as offices and buildings intended for civil use with a height of more than 24 meters. Suitable in indoor or outdoor environments even wet for fixed installation in free air, in pipe or duct, on masonry and structures metal or suspended.
REACTION TO FIRE SPECIFIC: Cables for general applications in construction work subject to reaction to fire requirements with reference to EU regulation 305/2011 and EN 50575:2014+A1:2016
SUITABLE FOR: Use in buildings and other civil engineering works in order to limit the generation and spread of fire and smoke toxic to humans and the environment. Possibility of being directly buried. Use even in wet rooms or outdoors (AD7). Good resistance to industrial oils and greases (ref. to CEI 20-67). For other details it is advisable to refer to CEI 20-67 “Guide to the use of 0.6/1 kV cables”.