FS17

DESCRIPTION

POWER CABLE, PVC INSULATED (S17 TYPE) WITH SPECIAL REQUIREMENTS OF REACTION TO FIRE ACCORDING TO CONSTRUCTION PRODUCTS REGULATION

SHAPE

Round

INSTALLATION

Fixed

CONDUCTOR

Flexible annealed copper cord, class 5 (EN 60228, IEC 60228)

INSULATION

Thermoplastic polyvinyl chloride compound S17 type with special requirements of reaction to fire performance according to Construction Product Regulation (CPR)

MAX MECHANICAL STRESS

5 Kg/mm²

MARKING

Engraving: PECSO MN FS17 450/750 V (SECTION) CEI-UNEL 35716 - IEMMEQU EFP - Cca s3, d1, a3 (BATCH) CE

COLOR

Standard colours: black, brown, blue 5010, blue 5015, grey, red, white, green/yellow, orange, pink, violet

VOLTAGE

450/750 V

MAXIMUM TEMPERATURE ON USE

70 ºC

MINIMUM TEMPERATURE OF INSTALLATION

5º C

MAXIMUM SHORT CIRCUIT TEMPERATURE

160° C

STANDARDS

CEI UNEL 35716 EN 50575:2014+A1 EN 50399 EN 60754-2 EN 61034-2 EN 60332-1-2

MINIMUM INTERNAL BENDING RADIUS

4xD

CERTIFICATIONS

click on the logos to download the certification

Guide to use

Cables for general application in construction works subject to fire resistance requirements
Cable compliant to CPR – Construction Product Regulation (UE 305/11)

ACCORDING TO CPR, CLASS Cca s3, d1, a3: Cables for general applications in construction works subject to fire resistance requirements. Provided by EN 50575: 2014 + A1.
Declaration of performance: DOP 00013.

SUITABLE FOR: Laying of bundled cables inside buildings and other civil engineering works, in order to limit the generation and spread of fire and toxic smoke dangerous for man and the environment